Schneider Electric ComPacT NSXm, new generation Circuit-breakers

General

  • Product range: ComPacT NSXm (new generation)
  • Type: Molded Case Circuit Breaker (MCCB)
  • Application: Distribution / line protection
  • Standards: IEC / EN 60947-2
  • Utilization category: Category A
  • Suitability for isolation: Yes

 Ratings (core requirement: up to 160 A)

  • Rated current (In): 16 → 160 A
  • Rated operational voltage (Ue): up to 690 V AC, 50/60 Hz
  • Network: AC systems

 Breaking capacity (Icu – typical ranges)

Depending on performance class (B, F, N):

  • 25 kA @ 415 V (B type)
  • 36 kA @ 415 V (F type)
  • 50 kA @ 415 V (N type)

 Insulation & dielectric properties

  • Rated insulation voltage (Ui): 800 V
  • Impulse withstand voltage (Uimp): 8 kV

 Trip units (protection technology)

Thermal-magnetic

  • TM-D (standard)
  • Protection: L (overload) + I (short-circuit)

Electronic (Micrologic)

  • Micrologic 2 / 4 / 5 (depending on model)
  • Functions:
    • L: overload
    • S: short-time
    • I: instantaneous
    • Optional R: earth leakage

 Protection functions

  • Overload protection (thermal/electronic)
  • Short-circuit protection
  • Optional:
    • Earth leakage (Vigi / integrated versions)
    • Adjustable protection curves
    • Energy metering (Micrologic)

 Mechanical & construction

  • Frame size: NSXm (compact frame)
  • Mounting:
    • Fixed
    • DIN rail (some models)
  • Poles:
    • 3P / 4P
  • Typical dimensions:
    • Width ≈ 80 mm
    • Height ≈ 137 mm

 Performance & durability

  • Mechanical durability: ~20,000 operations
  • Electrical durability:
    • Up to 10,000 cycles (depending on load)

Key features (new generation advantages)

  • Compact size (smallest in NSX range)
  • EverLink connectors (high reliability terminals)
  • Modular accessories (aux contacts, shunt trip, etc.)
  • Communication-ready (with Micrologic)
  • Optional integrated earth leakage protection