ABB Endura AZ40 Marine Boiler Oxygen and Combustibles COe Analyzer

Category:

Product Category

Combustion Oxygen and Carbon Monoxide Equivalent Analyzer

Product Overview

The ABB Endura AZ40 is a close-coupled combustion analyzer that continuously measures excess oxygen and unburned fuel in boiler, furnace and combustion exhaust gases.

Oxygen is measured using a zirconium-oxide cell, while unburned combustibles are detected by a catalytic sensor and reported as carbon monoxide equivalent—COe.

Simultaneous O₂ and COe measurement helps operators optimise the fuel-to-air ratio, reduce fuel consumption, identify burner problems and operate closer to the most efficient combustion point without creating unsafe conditions.

Main Components

  • In-situ sampling probe and filter
  • Heated sensor assembly
  • Zirconium-oxide oxygen sensor
  • Catalytic COe sensor
  • Air-powered sample ejector
  • Separate transmitter with colour display
  • Automatic calibration-gas control
  • Optional probe blowback system

Main Features

  • Simultaneous O₂ and COe measurement
  • Continuous extraction from the combustion process
  • Heated sample path prevents acid condensation
  • Primary and optional secondary probe filters
  • Programmable filter blowback
  • Automatic sensor calibration
  • NAMUR NE107 diagnostics
  • On-screen process trending
  • SD-card data and configuration storage
  • Six relay outputs
  • Four isolated analogue outputs
  • User-configurable digital I/O
  • RS-485/Modbus communication
  • Standard and high-temperature probes available

Technical Specifications

Specification Details
Oxygen measuring principle Zirconium-oxide cell
COe measuring principle High-sensitivity catalytic sensor
Minimum O₂ span 0–5%
Maximum O₂ span 0–25%
Minimum COe span 0–500 ppm
Maximum COe span 0–20,000 ppm/2%
Process-temperature measurement Up to approximately 1,649°C
Transmitter ambient temperature –20°C to +55°C
Sensor ambient temperature –20°C to +70°C
Transmitter protection IP55/NEMA 4
Sensor protection IP66/NEMA 4X
Analogue outputs Four isolated, programmable 0–20 mA
Relay outputs Six normally closed relays
Digital I/O Two configurable inputs or outputs
Communication RS-485/Modbus
Transmitter weight Approximately 7.6 kg
Instrument-air supply 350–700 kPa
Maximum installation altitude 2,000 metres

Probe Temperature Ratings

Probe Arrangement Maximum Process Temperature
Standard probe with primary filter 649°C
Standard probe with primary and secondary filters 816°C
600 mm high-temperature probe 1,650°C
900 mm high-temperature probe 1,370°C
1,200 mm high-temperature probe 1,232°C

Final temperature suitability depends on the complete probe, filter and installation arrangement.

Marine and Offshore Applications

  • Marine auxiliary boilers
  • Oil-fired main boilers
  • Exhaust-gas boilers
  • Waste-heat recovery systems
  • Incinerators
  • Offshore process heaters
  • FPSO boiler combustion systems
  • Refinery furnaces
  • Power-generation boilers
  • Petrochemical heaters
  • Burner-management optimisation
  • Combustion troubleshooting and emissions reduction

Marine installation suitability and classification requirements must be confirmed for the selected configuration.

Operational Benefits

  • Improves boiler combustion efficiency
  • Reduces excess-air operation
  • Helps lower fuel consumption
  • Identifies incomplete combustion
  • Detects burner or fuel-distribution problems
  • Reduces carbon monoxide emissions
  • Supports safer fuel-to-air ratio control
  • Provides early warning of deteriorating combustion
  • Reduces probe maintenance through automatic blowback