Autronica AutroFlame X98AF Single-IR Flame Detector

Category:

Product Overview

The AutroFlame X98AF is an explosion-protected infrared flame detector designed for rapid fire detection in marine, offshore and heavy-industrial environments.

Its Time Domain Signal Analysis technology provides strong immunity against background infrared radiation from heaters, turbines and ovens. It is especially suitable for contaminated or dirty areas where reliable detection and low maintenance are essential.

Main Features

  • High-speed infrared flame detection
  • Response as fast as 40 milliseconds on selected models
  • Time Domain Signal Analysis
  • Strong rejection of false-alarm sources
  • Automatic, manual and magnetic optical-integrity testing
  • Microprocessor-controlled heated optics
  • Fire, fault and auxiliary relays
  • Optional isolated 0–20 mA output
  • Optional HART communication
  • Modbus RS-485 communication
  • Built-in event logging
  • Three-colour status indicator
  • Aluminium or 316 stainless-steel housing
  • Explosion-protected for hazardous areas
  • Suitable for indoor and outdoor installation

Technical Specifications

Specification Details
Detection technology Infrared
Nominal voltage 24 VDC
Operating-voltage range 18–30 VDC
Minimum power consumption 2.1 W at 24 VDC
Maximum consumption 16.5 W at 30 VDC
Relay-contact rating 5 A at 30 VDC
Analogue output Optional 0–20 mA
Communication HART and Modbus RS-485 options
Operating temperature –40°C to +75°C
Storage temperature –55°C to +85°C
Humidity 0–95% RH
Protection rating IP66 / NEMA 4X
Field of view 90° cone
Aluminium weight Approximately 2.75 kg
Stainless-steel weight Approximately 4.5 kg
Cable entry ¾-inch NPT or M25
Standard EN 54-10
ATEX certificate DEMKO 02 ATEX 132195X
IECEx certificate IECEx ULD 06.0018X

Detection Examples

Fire source Detection distance Typical response
n-Heptane, 1 × 1 ft fire 25.9 m 15 seconds
Methane, 32-inch plume 18.3 m 5 seconds
Propane torch 0.6 m 0.04 seconds

Performance depends on sensitivity settings, environmental conditions, fire size and installation angle.

Typical Applications

  • Ship and offshore machinery spaces
  • Turbine enclosures
  • Petrochemical facilities
  • Refineries
  • Fuel-handling areas
  • Paint and powder-coating facilities
  • Dirty industrial environments
  • Generator rooms
  • Compressor stations
  • Outdoor hazardous areas

Installation Notes

The detector is supplied without its swivel mount. The correct mounting bracket, cable glands and certified blanking plugs must be selected separately according to the housing material, cable-entry type and hazardous-area certification.