Schneider electric ComPacT for DC networks, new generation circuit breaker

Category:

General

  • Product range: ComPacT NSX DC
  • Type: Molded Case Circuit Breaker (MCCB) for DC
  • Application:
    • DC distribution systems
    • Photovoltaic (PV)
    • Marine & telecom systems
  • Standards:
    • IEC / EN 60947-2 (circuit breakers)
    • IEC / EN 60947-3 (switch-disconnectors)

 Ratings (DC line protection up to 630 A)

  • Rated current (In):
    • 16 → 600 A (standard DC breakers)
    • Up to 630 A (via configurations / switch-disconnector / parallel poles)
  • Number of poles:
    • 1P / 2P / 3P / 4P (depending on voltage & application)

 Voltage ratings (DC)

  • Rated operational voltage (Ue):
    • Up to 750 V DC (standard distribution)
    • Up to 1000 V / 1500 V DC (PV-specific versions)
  • Configuration:
    • Series or parallel pole connection for higher voltage/current

 Breaking capacity (Icu)

  • Typical DC breaking capacity:
    • Up to 100 kA @ 750 V DC (depending on poles/configuration)
  • Service breaking capacity:
    • Ics = 100% of Icu (high reliability)

 Insulation & dielectric characteristics

  • Rated insulation voltage (Ui): 750 V DC
  • Impulse withstand voltage (Uimp): 8 kV
  • Pollution degree: 3

 Trip units (DC protection)

Thermal-magnetic (main technology)

  • Used across DC range
  • Types:
    • TM-D / TM-DC / TM-G
  • Functions:
    • Overload protection (thermal)
    • Short-circuit protection (magnetic)

Magnetic-only (high current frames)

  • For 400 A / 630 A
  • Adjustable instantaneous protection levels

 Protection functions

  • Overload (long-time)
  • Short-circuit (instantaneous)
  • Designed for:
    • DC fault interruption (fast arc extinction)
    • High L/R time constant systems

 Mechanical & construction

  • Versions:
    • Fixed
    • Plug-in
    • Withdrawable
  • Mounting:
    • Vertical / horizontal / flat (no derating)
  • Poles configurable in:
    • Series (increase voltage)
    • Parallel (increase current)

 Performance

  • Breaking time: < 10 ms
  • Mechanical durability:
    • Up to 10,000 operations
  • Electrical durability:
    • Up to 5,000 cycles (at In)

 Environmental conditions

  • Operating temperature: –25°C to +70°C
  • Storage temperature: –50°C to +85°C
  • Altitude: up to 2000 m (typical without derating)

 Key features (DC new generation)

  • High-performance DC arc interruption chambers
  • Flexible series / parallel pole configurations
  • Compatibility with AC NSX accessories
  • Suitable for:
    • Floating, grounded, or mid-point DC systems
  • Full isolation capability (positive break indication)

 Typical models (DC ≤630 A)

  • NSX100 DC
  • NSX160 DC
  • NSX250 DC
  • NSX400 DC
  • NSX630 DC

Engineering notes (important for DC systems)

  • DC breaking requires pole combinations → rating depends on:
    • Number of poles used
    • Voltage level (e.g., 2P = 500 V, 3P = 750 V)
  • Always verify:
    • L/R time constant
    • Pole wiring configuration
    • Application type (PV, battery, telecom)