General
- Product range: ComPacT NSX (new generation)
- Type: Molded Case Circuit Breaker (MCCB)
- Application: Power distribution / feeder protection
- Standards: IEC / EN 60947-2
- Utilization category: Category A
- Suitability for isolation: Yes (fully compliant MCCB)
Electrical ratings
- Rated current (In): 16 → 630 A
- Rated operational voltage (Ue): up to 690 V AC (50/60 Hz)
- Network: AC systems
Breaking capacity (Icu)
Depends on performance class:
- B (Basic): ~25 kA @ 415 V
- F / N / H / S / L classes:
- Up to 70 kA @ 415 V (H type)
- Higher classes available (up to ~150–200 kA depending on frame – per catalogue)
Insulation & dielectric characteristics
- Rated insulation voltage (Ui): 800 V
- Impulse withstand voltage (Uimp): 8 kV
Trip units
Thermal-magnetic (TM-D)
- Functions:
- L: overload (thermal)
- I: instantaneous short-circuit
- Adjustable overload (Ir ≈ 0.7–1 × In)
Electronic (Micrologic)
- Types: Micrologic 2 / 5 / 6
- Protection:
- L: long-time
- S: short-time
- I: instantaneous
- G: earth fault (optional)
- Additional:
- Energy metering
- Communication (EcoStruxure ready)
Protection functions
- Overload protection
- Short-circuit protection
- Optional:
- Earth leakage (Vigi / Micrologic)
- Zone Selective Interlocking (ZSI)
- Measurement & communication
Mechanical characteristics
- Mounting:
- Fixed
- Plug-in
- Withdrawable
- Poles:
- 3P / 4P
- Typical dimensions (NSX100 frame):
- Height: ~161 mm
- Width: ~105 mm
- Depth: ~86 mm
Performance & durability
- Mechanical durability: up to 50,000 operations
- Electrical durability:
- Up to 30,000 cycles (at rated conditions)
Environmental conditions
- Operating temperature: –25°C to +70°C
- Storage: –50°C to +85°C
- Pollution degree: 3
- Altitude: up to 2000 m without derating
Key features (new generation)
- Compact design with improved performance
- EverLink terminals (reduced overheating risk)
- Digital-ready (EcoStruxure Power integration)
- Integrated metering & diagnostics
- Modular accessories (aux contacts, shunt trip, motor operator)
- Improved installation (DIN rail, spring auxiliaries)
Typical models
- NSX100 / NSX160 / NSX250 / NSX400 / NSX630
- Breaking capacity classes: B, F, N, H, S, L
- Trip units: TM-D or Micrologic