Autronica AutroFlame X33AF Multispectrum IR Flame Detector

Category:

Product Overview

The AutroFlame X33AF is a multispectrum infrared flame detector designed for rapid detection of fires involving light and heavy hydrocarbon fuels.

It uses three infrared sensors with advanced signal-processing technology to distinguish genuine flames from sunlight, hot equipment, welding activity and other potential false-alarm sources. Its explosion-protected construction makes it suitable for demanding marine, offshore and oil-and-gas applications.

Main Features

  • Three-spectrum infrared flame detection
  • Long-range hydrocarbon-fire detection
  • High resistance to false alarms
  • Multiple selectable sensitivity levels
  • Automatic optical integrity testing
  • Microprocessor-controlled heated optics
  • Operates in dirty and adverse weather conditions
  • Built-in event logging with date and time
  • Fire, fault and auxiliary relay outputs
  • Optional 0–20 mA output with HART communication
  • SIL 2-capable versions available
  • Aluminium and 316 stainless-steel housings
  • Suitable for indoor and outdoor installation
  • Explosion-proof hazardous-area construction

Automatic Optical Integrity

The detector automatically performs a calibrated optical-path and sensor-performance test. This verifies the detector’s operational condition without requiring routine testing with an external flame-test lamp.

Technical Specifications

Specification Details
Detection principle Three-spectrum infrared
Nominal operating voltage 24 VDC
Operating-voltage range 18–30 VDC
Power consumption 4 W minimum without heater
Maximum consumption 17 W at 30 VDC with heater and EOL resistor
Analogue output Optional isolated 0–20 mA
Communication Optional HART
Relay rating 5 A at 30 VDC
Standard operating temperature –40°C to +75°C
Extended hazardous rating Up to –55°C to +125°C, model dependent
Humidity 0–95% RH; withstands short periods of condensation
Protection rating IP66/IP67
Enclosure options Painted copper-free aluminium or 316 stainless steel
Field of view 90° horizontal × 75° vertical
Cable entry ¾-inch NPT or M25, version dependent
Functional-safety option SIL 2 capable
Standard EN 54-10
ATEX certificate DEMKO 01 ATEX 130204X
IECEx certificate IECEx ULD 06.0017X
Marine approval DNV and US Coast Guard options

Detection Performance Examples

Performance depends on the selected sensitivity, fuel, flame size and environmental conditions.

Fuel/fire example Maximum stated distance
n-Heptane fire Up to approximately 80.7 m
Diesel fire Up to approximately 53.3 m
Methane plume Up to approximately 38.1 m
Propane plume Up to approximately 38.1 m
Methanol fire Up to approximately 45.7 m
Jet fuel fire Up to approximately 71.6 m

Typical Applications

  • LNG and LPG carriers
  • Oil and chemical tankers
  • FPSOs and offshore platforms
  • Refineries and petrochemical plants
  • Compressor stations
  • Turbine enclosures
  • Loading racks and fuel terminals
  • Gas-processing facilities
  • Aircraft hangars
  • Engine and machinery spaces

Available Configurations

  • Painted aluminium housing
  • 316 stainless-steel housing
  • Relay and analogue-output versions
  • HART-enabled versions
  • SIL 2-certified configurations
  • X33AF PL models for AutroSafe PowerLoop systems
  • Standard and extended-temperature versions

The exact part number must be selected according to housing material, cable entry, certification, output and communication requirements.