Product Overview
The AutroFlame X32AF is a specialized multispectrum infrared detector engineered to detect nearly invisible hydrogen flames.
It monitors the water-band infrared emissions produced by hydrogen combustion, allowing it to detect fires that may generate little or no carbon dioxide. Advanced signal processing provides strong flame sensitivity while rejecting false alarms from sunlight, artificial lighting, lightning and hot equipment.
Main Features
- Specialized detection of invisible hydrogen flames
- Multispectrum infrared detection technology
- Detection range up to approximately 30 metres
- Rapid detection of hydrogen and methanol fires
- High immunity to sunlight and artificial lighting
- Multiple selectable sensitivity levels
- Automatic optical-integrity testing
- Microprocessor-controlled heated optics
- Fire, fault and auxiliary relay outputs
- Optional 0–20 mA and HART communication
- SIL 2-capable configurations
- Aluminium and 316 stainless-steel versions
- Explosion-protected construction
- Suitable for harsh indoor and outdoor locations
Technical Specifications
| Specification | Details |
|---|---|
| Detection principle | Multispectrum infrared |
| Primary application | Hydrogen and low-carbon flames |
| Nominal voltage | 24 VDC |
| Operating-voltage range | 18–30 VDC |
| Minimum power consumption | 4 W without heater |
| Maximum consumption | 17 W at 30 VDC |
| Relay-contact rating | 5 A at 30 VDC |
| Analogue output | Optional 0–20 mA |
| Communication | Optional HART |
| Operating temperature | –40°C to +75°C |
| Extended-temperature option | –55°C to +125°C |
| Storage temperature | –55°C to +85°C |
| Humidity | 0–95% RH |
| Protection rating | IP66/IP67 |
| Field of view | 90° horizontal × 75° vertical |
| Housing options | Copper-free aluminium or 316 stainless steel |
| Cable entry | ¾-inch NPT or M25 |
| Approximate aluminium weight | 3.2 kg |
| Approximate stainless-steel weight | 6.3 kg |
| Functional safety | SIL 2-capable versions |
| Part number | 116-029009-002 |
Detection Performance
| Flame type | Test condition | Detection distance | Typical response |
|---|---|---|---|
| Hydrogen | 30-inch plume at 100 SLPM | 30.5 m | Approximately 3 seconds |
| Methanol | 1 × 1 ft fire | 21.3 m | Approximately 5 seconds |
Actual performance depends on the selected sensitivity, installation angle, environmental conditions and fire characteristics.
Typical Applications
- Hydrogen-fuelled vessels
- Hydrogen storage facilities
- Fuel-cell installations
- Hydrogen compressor rooms
- Hydrogen-cooled generators
- Refineries and petrochemical plants
- Chemical-loading facilities
- Gas-processing plants
- Fertilizer plants
- Aircraft and vehicle hangars
Certification and Protection
- FM 3260
- EN 54 certification
- SIL 2-capable versions
- ATEX-compliant models
- IECEx ULD 06.0017X
- Ex d or Ex d e configurations
- IP66/IP67 environmental protection