Teledyne Oldham Simtronics GD10P Infrared Point Gas Detector

Category:

Product Overview

The Teledyne Oldham Simtronics GD10P is a fixed infrared point gas detector designed for continuous monitoring of combustible hydrocarbon gases.

It uses a patented solid-state infrared source instead of a conventional filament lamp, providing excellent stability, fast response and exceptionally low maintenance. Its stainless-steel construction, heated optics and hazardous-area certifications make it especially suitable for ships, FPSOs, offshore platforms and petrochemical installations.

Technical Specifications

Specification Details
Manufacturer Teledyne Oldham Simtronics
Exact model GD10P
Available model references GD10-P00 and GD10-PE0
Detector type Fixed infrared point gas detector
Detection technology Dual-wavelength, dual-path infrared absorption
Detected gases Hydrocarbon gases
Standard gas ranges Methane or propane: 0–100% LEL or 0–100% volume
Other flammable gases 0–100% LEL
Accuracy from 0–50% ±3% of full scale
Accuracy from 50–100% ±5% of full scale
T20 response Approximately 0.7 seconds
T50 response Approximately 1.7 seconds
T90 response Approximately 4 seconds
Standard output 4–20 mA current source
Optional output 4–20 mA current sink
Communication HART 7
Maximum load impedance 500 ohms
Power supply 18–32 VDC, nominally 24 VDC
Power consumption Approximately 3.5 W
Electrical connection Three-wire shielded cable
Cable entry M20 Ex e cable gland
Operating temperature −40°C to +60°C
Storage temperature −40°C to +70°C
Operating humidity 0–100% RH
Ingress protection IP66/IP67
Housing material ASTM 316 stainless steel
Dimensions 264 × 104 × 106 mm
Weight Approximately 2.9 kg
Calibration Factory calibrated; no routine field recalibration
Self-testing Continuous optical and electronic self-test

Key Features

  • Patented solid-state SimSource infrared technology
  • No oxygen required for correct gas measurement
  • Immune to catalytic-sensor poisoning from silicone vapours and H₂S
  • Continuous internal self-diagnostics
  • Early dirty-optics warning
  • Heated optics help prevent condensation
  • No saturation-related false readings
  • Gas velocity does not affect measurement accuracy
  • Factory calibrated with no routine field recalibration
  • Fail-safe output and configurable fault levels
  • Suitable for high-demand SIL 2 safety applications
  • Rugged stainless-steel explosion-protected housing

Fault Output Levels

Condition Output
Normal gas measurement 4–20 mA
Preventive optics warning 2 mA
Dirty optics 1 mA
Internal detector fault 0 mA

Certifications and Approvals

  • ATEX
  • IECEx
  • INMETRO
  • CNEX
  • PESO
  • Ex db eb IIC T6 Gb
  • CSA and applicable North American approvals
  • SIL 2 SC3 High Demand
  • Marine Equipment Directive
  • ABS marine approval

Typical Applications

  • LNG and LPG carriers
  • Oil and chemical tankers
  • FPSOs and offshore platforms
  • Gas compressor rooms
  • Boiler and machinery spaces
  • Fuel-gas supply systems
  • Drilling rigs and MODUs
  • Refineries and petrochemical plants
  • Hazardous machinery compartments
  • Gas turbine enclosures