Autronica AutroFlame X32AF Hydrogen Flame Detector

Category:

Product Overview

The AutroFlame X32AF is a specialized multispectrum infrared detector engineered to detect nearly invisible hydrogen flames.

It monitors the water-band infrared emissions produced by hydrogen combustion, allowing it to detect fires that may generate little or no carbon dioxide. Advanced signal processing provides strong flame sensitivity while rejecting false alarms from sunlight, artificial lighting, lightning and hot equipment.

Main Features

  • Specialized detection of invisible hydrogen flames
  • Multispectrum infrared detection technology
  • Detection range up to approximately 30 metres
  • Rapid detection of hydrogen and methanol fires
  • High immunity to sunlight and artificial lighting
  • Multiple selectable sensitivity levels
  • Automatic optical-integrity testing
  • Microprocessor-controlled heated optics
  • Fire, fault and auxiliary relay outputs
  • Optional 0–20 mA and HART communication
  • SIL 2-capable configurations
  • Aluminium and 316 stainless-steel versions
  • Explosion-protected construction
  • Suitable for harsh indoor and outdoor locations

Technical Specifications

Specification Details
Detection principle Multispectrum infrared
Primary application Hydrogen and low-carbon flames
Nominal voltage 24 VDC
Operating-voltage range 18–30 VDC
Minimum power consumption 4 W without heater
Maximum consumption 17 W at 30 VDC
Relay-contact rating 5 A at 30 VDC
Analogue output Optional 0–20 mA
Communication Optional HART
Operating temperature –40°C to +75°C
Extended-temperature option –55°C to +125°C
Storage temperature –55°C to +85°C
Humidity 0–95% RH
Protection rating IP66/IP67
Field of view 90° horizontal × 75° vertical
Housing options Copper-free aluminium or 316 stainless steel
Cable entry ¾-inch NPT or M25
Approximate aluminium weight 3.2 kg
Approximate stainless-steel weight 6.3 kg
Functional safety SIL 2-capable versions
Part number 116-029009-002

Detection Performance

Flame type Test condition Detection distance Typical response
Hydrogen 30-inch plume at 100 SLPM 30.5 m Approximately 3 seconds
Methanol 1 × 1 ft fire 21.3 m Approximately 5 seconds

Actual performance depends on the selected sensitivity, installation angle, environmental conditions and fire characteristics.

Typical Applications

  • Hydrogen-fuelled vessels
  • Hydrogen storage facilities
  • Fuel-cell installations
  • Hydrogen compressor rooms
  • Hydrogen-cooled generators
  • Refineries and petrochemical plants
  • Chemical-loading facilities
  • Gas-processing plants
  • Fertilizer plants
  • Aircraft and vehicle hangars

Certification and Protection

  • FM 3260
  • EN 54 certification
  • SIL 2-capable versions
  • ATEX-compliant models
  • IECEx ULD 06.0017X
  • Ex d or Ex d e configurations
  • IP66/IP67 environmental protection